SC (B) 11 series three-phase resin insulation dry-type power transformer

SC (B) 11 series three-phase resin insulation dry-type power transformer

Less SC (b) 11 series of epoxy resin casting has excitation regulating dry type transformer is used with packing in the class F epoxy resin mixture, after vacuum thin film degassing, under vacuum and pressure, the outer surface of the thin layer pouring placed in glass filament reinforced the high-low voltage coil.
SC (B) 11 series three-phase resin insulation dry-type power transformer
Product Description

General

Less SC (b) 11 series of epoxy resin casting has excitation regulating dry type transformer is used with packing in the class F epoxy resin mixture, after vacuum thin film degassing, under vacuum and pressure, the outer surface of the thin layer pouring placed in glass filament reinforced the high-low voltage coil. Is a kind of mechanical strength, electrical strength, high heat strength of the dry type transformer. Is an excellent product of urban power grid transformation, especially suitable for high-rise buildings, airports, power plants, commercial centers and other requirements of fire, explosion, moisture is an important place.

 

Product features

Flame retardant,explosion-proof and maintenance-free and no installations are allowed and save your cost.

Economic due to low loss and good conservation of power.

Partial discharge is less than 10pc;high mechanical strength and reliability;moisture resistance and dust protection.

Anti-shortcircuit;good performance to withstand the lighting impulse.

The outer casing is made of iron and alumin alloy.There are different case tyes and modes fo wiring at your choice.

The transformer can be equipped With temperature control & display system according to the specific requirement. Lt can be coop-erated with the temperature control system.

 

Notice to orderer

Please provide the following parameter when Ordeing:

1、Product type

2、Rated capacity

3、Voltage combination

4、Regulating range

5、Frequency

6、Connectin Symbol

7、Shortn-circuit impedance

8、For special requirement,giving the technical requirement.

 

Technical performance parameters

Model
Rated Current
(A)
Voltage Combution
Connection symbol
No-load Current
(%)
No-loadLoos
(W)
Load Loos(120℃)
(w)
Lmpedance Voltage
UK(%)
H.V.(KV)
L.V.(KV)
SC11-30
1.73
43.3


±2x2.5%

6.3±
±2x2.5%

10±
±2x2.5%

10.5±
±2x2.5%

11±
±2x2.5%

0.4
Dyn11
 
 
 
YynO
2.5
168
710
4
SC11-50
1.73
43.3
2.2
238
1000
SC11-80
4.62
115.5
2.1
322
1380
SC11-100
5.77
144.3
1.9
350
1570
SC11-125
7.22
180.4
1.7
413
1850
SC11-160
7.22
180.4
1.7
476
2130
SC11-200
11.6
288.7
1.5
546
2530
SC11-250
14.43
360.8
1.5
630
2760
SC11-315
18.19
454.7
1.3
770
3470
SC(B)11-400
23.09
577.4
1.3
854
3990
SC(B)11-500
28.9
721.7
1.3
1015
4880
SC(B)11-630
36.4
909
1.2
1176
5880
SC(B)11-630
36.4
909
1.2
1134
5960
6
SC(B)11-800
46.2
1154.7
1.2
1330
6960
SC(B)11-1000
57.7
1443.4
1
1547
8130
SC(B)11-1250
72.2
1804.3
1
1827
9690
SC(B)11-1600
92.4
2309
1
2142
11730
SC(B)11-2000
115.5
2886.7
0.9
2905
14450
SC(B)11-2500
144.3
3608.4
0.9
3500
17170

 

Keyword:
strength
voltage

Related Products

Messages
If you are interested in our products, please fill in the following form, we will contact you in time! Service hotline: 86-513-88780188
全部评论
已有0条评论
There is currently no content to display
Please add data record on website background.

Jiangsu Ming’an Electrical Co., Ltd.

Service Hotline:

Add:

Hai’an Industry Park, Hai’an County, Jiangsu

Copyright © 2021  Jiangsu Ming’an Electrical Co., Ltd.    苏ICP备09048167