XGN-12(SF6) Type AC High-Voltage Sulfur Hexafluoride Ring Main Unit
Keywords:
XGN-12(SF6) Type AC High-Voltage Sulfur Hexafluoride Ring Main Unit
Category:
Product Description
Overview
The XGN‑12(SF6) type AC high‑voltage sulfur hexafluoride ring‑main switchgear (hereinafter referred to as the ring‑main cabinet) is a new generation of high‑voltage electrical equipment independently designed and developed by our factory, incorporating advanced foreign technologies and tailored to meet the requirements of rural power‑grid modernization and urban grid renovation in China. Following rigorous type tests and extended trial‑operation evaluations, all technical performance parameters have fully complied with IEC 298 and GB 3906 standards. The ring‑main cabinet is equipped with either an FLN‑12(SF6) load switch or an FLN‑12(SF6) load switch–fuse combination unit. Because SF6 gas serves as both the arc‑extinguishing and insulating medium, compared with vacuum load switches that use vacuum for arc extinction, SF6 switches provide “soft” breaking, eliminating the need to install surge arresters or other components in the primary wiring scheme to protect against overvoltages. The cabinet body is fabricated from imported aluminum‑zinc coated steel sheets, precision‑machined on CNC equipment and assembled by riveting, achieving an ingress protection rating of IP4X and featuring reliable mechanical interlocks and anti‑misoperation safeguards. This product boasts highly distinctive advantages, including compact size, light weight, aesthetically pleasing appearance, simple operation, long service life, high performance parameters, zero environmental pollution, and minimal maintenance requirements.
Product Model and Its Meaning

Technical Performance Parameters
|
Name
|
Unit
|
Parameter
|
| Rated voltage |
KV
|
12
|
| Rated frequency |
Hertz
|
50
|
| Rated current of the main busbar |
A
|
630
|
| Rated short-time withstand current of the main circuit and the grounding circuit |
KA/S
|
Main circuit: 20/3
Grounding circuit: 20/2 |
| Rated short-time withstand current of the main circuit and the grounding circuit |
KA
|
50
|
| Rated short-time withstand current of the main circuit and the grounding circuit |
KA
|
50 (with fuse)
|
| Number of full-capacity interruptions by the load switch |
Next
|
100
|
| Fuse interrupting current |
KA
|
31.5, 40. 50
|
| Mechanical life |
Next
|
2000
|
| 1-minute power-frequency withstand voltage (peak value), phase-to-phase, phase-to-ground / isolation gap |
KV
|
42/48
|
| Lightning impulse withstand voltage (RMS), phase-to-phase, phase-to-ground / isolation gap |
KV
|
75/85
|
| 1-minute power-frequency withstand voltage of the secondary circuit |
KV
|
2
|
| Protection rating |
|
IP4X
|
Installation Diagram

Related products
Product Inquiry
Company Address: Hai’an Industry Park, Hai’an County, Jiangsu
Sales Hotline:0086-0513-88780188
After-sales service:0086-0513-88782288
Fax: 0086-0513-88782959
Postal code: 226600
Website:www.jsmadq.com
Email:jsmadq@sina.com 2930515310@qq.com
Scan to view the mobile version
无数据提示