S13-M Series (20 kV) Three-Phase Fully Sealed Oil-Immersed Distribution Transformer

The S11-M and S13-M (20 kV) series fully sealed distribution transformers use the corrugated tank fins as heat‑dissipating cooling elements. These fins expand and contract with changes in the oil level, isolating the transformer interior from the atmosphere and preventing oil degradation, insulation moisture absorption, and aging, thereby enhancing operational reliability. The tank welds are full, smooth, even in thickness, and ensure leak‑proof integrity. The core is constructed from 0.23 mm high‑permeability laser‑grooved laminations arranged in a stepped five‑step joint structure, which helps reduce no‑load losses and no‑load current, making this a new generation of environmentally friendly products. Anti‑looseness nuts are used to secure and clamp the core. The high‑voltage windings are multi‑layered, with interlayer insulation provided by adhesive‑coated paper to enhance mechanical strength. The low‑voltage windings are either layered or of a novel helical design; interlayer insulation also employs adhesive‑coated paper, and the low‑voltage windings feature formed end rings that provide gapless, full support, ensuring excellent mechanical strength. For pressure protection, a pressure relief valve is installed; for gas protection, QJ4‑type gas relays are used for units above 800 kVA. Units of 1,000 kVA and above are equipped with remote‑readout temperature gauges for monitoring oil temperature at a distance.

Keywords:

S13-M Series (20 kV) Three-Phase Fully Sealed Oil-Immersed Distribution Transformer

Product Inquiry:

Product Description

  Product Overview:


    The S11-M and S13-M (20 kV) series fully sealed distribution transformers use the corrugated tank fins as heat‑dissipating cooling elements. These fins expand and contract with changes in the oil level, isolating the transformer interior from the atmosphere and preventing oil degradation, insulation moisture absorption, and aging, thereby enhancing operational reliability. The tank welds are full, smooth, even in thickness, and ensure leak‑proof integrity. The core is constructed from 0.23 mm high‑permeability laser‑grooved laminations arranged in a stepped five‑step joint structure, which effectively reduces no‑load losses and no‑load current, making this a new generation of environmentally friendly products. Anti‑looseness nuts are employed for core clamping and tightening. The high‑voltage windings are multi‑layered, with interlayer insulation provided by adhesive‑coated paper to enhance mechanical strength. The low‑voltage windings are either layered or of a novel helical design, also using adhesive‑coated paper for interlayer insulation; their end turns are formed to provide gapless, complete support, ensuring excellent mechanical strength. For pressure protection, a pressure relief valve is installed; for gas‑related protection, QJ4‑type gas relays are used for units above 800 kVA. Units of 1,000 kVA and above are equipped with remote‑readout temperature gauges for monitoring oil temperature at a distance.

 

  Ordering Instructions:
  When placing your order, please provide the following parameters:
  1. Product Model
  2. Rated Capacity
  3. Voltage Combination
  4. Scope of Adjustment
  5. Frequency
  6. Connection Group Designation
  7. Short-circuit impedance
  8. For products with special requirements, specify the technical specifications.

 

  Technical Data Sheet for the S13-M Series (20 kV) Three-Phase Fully Sealed Oil-Immersed Distribution Transformer

 

Rated

Capacity

( k VA)

Rated voltage

Connection

Group

No-load current ( %)

No-load loss ( W)

Load loss ( W)

Impedance voltage ( %)

High pressure ( kV )

Low pressure ( kV )

30

20

±2×2.5%

or

22

±2×2.5%

or 24

±2×2.5%

 

0.4

Yyn0

Dyn11

2.1

70

640/690

5.5

 

50

2.0

100

960/1010

80

1.8

140

1370/1440

100

1.6

160

1650/1730

125

1.5

190

1980/2080

160

1.4

230

2420/2540

200

1.3

270

2860/3000

250

1.2

320

3320/3520

315

1.1

380

4010/4210

400

1.0

455

4730/4970

500

1.0

545

5660/5940

630

0.9

645

6820

6

800

0.8

780

8250

1000

0.7

920

11330

1250

0.7

1080

13200

1600

0.6

1300

15950

2000

0.6

1565

19140

2500

0.5

1870

22220

Note: For transformers with a rated capacity of 500 kVA or less, the load loss values above the diagonal line in the table apply to the Yyn0 connection group, while those below the diagonal line apply to the Dyn11 connection group.

Related products

Product Inquiry

If you have any needs, please feel free to contact us.
SAF Coolest v1.3.1.1 设置面板GAGSE-AGYF-JSAFE-ZFZ
图片ALT信息: Ming’an
违禁词: First, the best, top-tier, leading, one-of-a-kind, king, industry leader, pioneer, ultimate,

无数据提示

Sorry, this section is currently being updated. Please stay tuned!

You can view other sections or return to the previous page.Home

V1.3.1 SVG图标库请自行添加图标,用div包起来,并命名使用