S11-M Series (20 kV) Three-Phase Fully Sealed Oil-Immersed Distribution Transformer
Keywords:
S11-M Series (20 kV) Three-Phase Fully Sealed Oil-Immersed Distribution Transformer
Category:
Product Description
Product Overview:
The S11-M and S13-M (20 kV) series fully sealed distribution transformers use the corrugated tank fins as heat‑dissipating cooling elements. These fins expand and contract with changes in the oil level, isolating the transformer interior from the atmosphere and preventing oil degradation, insulation moisture absorption, and aging, thereby enhancing operational reliability. The tank welds are full, smooth, even in thickness, and ensure leak‑proof integrity. The core is constructed from 0.23 mm high‑permeability laser‑grooved laminations arranged in a stepped five‑step joint structure, which effectively reduces no‑load losses and no‑load current, making this a new‑generation environmentally friendly product. Anti‑loosening nuts are employed for core clamping and tightening. The high‑voltage windings are multi‑layered, with interlayer insulation provided by adhesive‑coated paper to enhance mechanical strength. The low‑voltage windings are either layered or of a novel helical design; interlayer insulation also utilizes adhesive‑coated paper, and the low‑voltage windings feature formed end rings that provide gapless, full support, ensuring excellent mechanical strength. For pressure protection, a pressure relief valve is installed; for gas protection, QJ4‑type gas relays are used for units above 800 kVA. Transformers rated at 1,000 kVA and above are equipped with remote‑readout temperature gauges for monitoring oil temperature.
Ordering Instructions:
When placing your order, please provide the following parameters:
1. Product Model
2. Rated Capacity
3. Voltage Combination
4. Scope of Adjustment
5. Frequency
6. Connection Group Designation
7. Short-circuit impedance
8. For products with special requirements, specify the technical specifications.
Technical Data Sheet for S11-M Series (20 kV) Three-Phase Fully Sealed Oil-Immersed Distribution Transformers
|
Rated Capacity ( k VA) |
Rated voltage |
Connection Group |
No-load current ( %) |
No-load loss ( W) |
Load loss ( W) |
Impedance voltage ( %) |
|
|
High pressure ( kV ) |
Low pressure ( kV ) |
||||||
|
30 |
20 ±2×2.5% or 22 ±2×2.5% or 24 ±2×2.5%
|
0.4 |
Yyn0 Dyn11 |
2.1 |
90 |
640/690 |
5.5
|
|
50 |
2.0 |
130 |
960/1010 |
||||
|
80 |
1.8 |
180 |
1370/1440 |
||||
|
100 |
1.6 |
200 |
1650/1730 |
||||
|
125 |
1.5 |
240 |
1980/2080 |
||||
|
160 |
1.4 |
290 |
2420/2540 |
||||
|
200 |
1.3 |
340 |
2860/3000 |
||||
|
250 |
1.2 |
400 |
3320/3520 |
||||
|
315 |
1.1 |
480 |
4010/4210 |
||||
|
400 |
1.0 |
570 |
4730/4970 |
||||
|
500 |
1.0 |
680 |
5660/5940 |
||||
|
630 |
0.9 |
810 |
6820 |
6 |
|||
|
800 |
0.8 |
980 |
8250 |
||||
|
1000 |
0.7 |
1150 |
11330 |
||||
|
1250 |
0.7 |
1350 |
13200 |
||||
|
1600 |
0.6 |
1630 |
15950 |
||||
|
2000 |
0.6 |
1960 |
19140 |
||||
|
2500 |
0.5 |
2340 |
22220 |
||||
Note: For transformers with a rated capacity of 500 kVA or less, the load loss values above the diagonal line in the table apply to the Yyn0 connection group, while those below the diagonal line apply to the Dyn11 connection group.
Related products
Product Inquiry
Company Address: Hai’an Industry Park, Hai’an County, Jiangsu
Sales Hotline:0086-0513-88780188
After-sales service:0086-0513-88782288
Fax: 0086-0513-88782959
Postal code: 226600
Website:www.jsmadq.com
Email:jsmadq@sina.com 2930515310@qq.com
Scan to view the mobile version
无数据提示
Sorry, this section is currently being updated. Please stay tuned!